Liquid-cooled commercial and industrial energy storage
Liquid-cooled commercial and industrial energy storage Liquid-cooled 261 capacity, modular design
Liquid-cooled commercial and industrial energy storage
Liquid-cooled 261 capacity, modular design
Device Structure Annotation
Rack
Liquid-cooled chassis
Central Control Display
PCS
Liquid Cooling System
High-voltage box
Fire Protection System
System Overview
Total Capacity: 261kWh
Rated Power: 125kW
Cooling Method: Liquid Cooling
Conversion rate: ≥90%
Charge/discharge duration: approximately 2 hours
Size: approx. 1.4m1m2.4m
Weight: 2.35T
Module Composition: 7
52.25kWh Battery Tray * 5
High-voltage box * 1
12 5KW PCS*1
Liquid Cooling Unit * 1
EMS*1
Alarm System * 1
Fire Protection System * 1
Technical Specifications
Table
Project | Specifications |
Model | 125kW/261kWh (Single Door) |
Battery Type | LFP |
Stored Energy (Total Capacity) | 261 kWh |
Rated Charge/Discharge Power | 125kW |
Rated Voltage | 832V |
Operating Voltage Range | 728V-936V |
Cycle Count | 8000 (Discharge Rate 0.5C EOL0%) |
Overall Cycle Efficiency | ≥90% |
Storage Temperature Range | -30℃-55℃ |
Best Operating Temperature | 10℃-35℃ |
Operating Relative Humidity | 10%-90% |
Storage and Transportation Relative Humidity | 5%-95% |
Rated Working Altitude | <3000m |
Communication Protocol | Supports IEC104, Modbus-RTU, DL/T645, and more. |
Size (L)WH (Dimension) | D1400W1000H2400mm |
Weight (Net Weight) | 2.35T |
Cooling Mode | Liquid Cooling |
PCS Parameters
Table
Project | Specifications |
Rated Output Power | 125kW |
Max AC Current | 216A |
Communication Interface | CAN/RS85 |
Rated Operating Voltage | 230/400V AC |
Rated Grid Frequency (Hz) | 50/60 |
AC Harmonic Voltage | <3% Linear Load |